What Size Tankless Water Heater Do I Need?
Two showers and a bathroom faucet running together take about 5 gpm of hot water. Raising it from 50 °F to 120 °F takes 175,000 BTU/h of heat, which a condensing gas unit gets from about 184,000 BTU/h of gas, and a standard unit from 213,000. In electric that is 51.2 kW.
Gas input for a condensing unit by what runs at once and the incoming water, with 120 °F hot water:
| Running at once | 40 °F | 50 °F | 70 °F |
|---|---|---|---|
| 1 shower | 84,000 | 74,000 | 53,000 |
| 1 shower + faucet | 126,000 | 111,000 | 79,000 |
| 2 showers | 168,000 | 147,000 | 105,000 |
| 2 showers + faucet | 211,000 | 184,000 | 132,000 |
| 3 showers | 253,000 | 221,000 | 158,000 |
| 2 showers, kitchen, dishwasher | 295,000 | 258,000 | 184,000 |
| Running at once | Flow | 40 °F | 50 °F | 60 °F | 70 °F |
|---|---|---|---|---|---|
| 1 shower | 2 gpm | 84,000 | 74,000 | 63,000 | 53,000 |
| 1 shower + faucet | 3 gpm | 126,000 | 111,000 | 95,000 | 79,000 |
| 2 showers | 4 gpm | 168,000 | 147,000 | 126,000 | 105,000 |
| 2 showers + faucet | 5 gpm | 211,000 | 184,000 | 158,000 | 132,000 |
| 3 showers | 6 gpm | 253,000 | 221,000 | 189,000 | 158,000 |
| 2 showers, kitchen, dishwasher | 7 gpm | 295,000 | 258,000 | 221,000 | 184,000 |
Tankless heaters are rated by the temperature rise they give at a flow, so the same unit delivers far less in a cold climate: Rinnai rates one 160,000 BTU/h model at 5.7 gpm with 77 °F water and 2.9 gpm with 35 °F water. Size for the coldest month.
How to Size a Tankless Water Heater
- 1List the hot water fixtures that may run at the same time, such as two showers and a bathroom sink.
- 2Add their hot water flows in gallons per minute.
- 3Subtract the coldest incoming water temperature from the hot water setting, usually 120 °F, for the rise.
- 4Find the heat: gpm × rise × 500 BTU/h, then divide by the unit's efficiency for gas input, or by 3,412 for kW.
The fixtures add up at the heater:
The 500 is the weight of a gallon of water, 8.33 lb, times 60 minutes. In metric, kW = L/min × rise in °C ÷ 14.36: 18.93 L/min heated from 10 °C to 49 °C needs 51.4 kW.
Hot Water Flow per Fixture
The calculator counts the hot water each fixture draws, less than its full flow because cold water mixes in at the tap:
| Fixture | Hot water | Federal limit | WaterSense |
|---|---|---|---|
| Shower | 2 gpm | 2.5 gpm | 2.0 gpm |
| Bathroom faucet | 1 gpm | 2.2 gpm | 1.5 gpm |
| Kitchen faucet | 1.5 gpm | 2.2 gpm | — |
| Dishwasher | 1.5 gpm | — | — |
| Washer on hot | 2 gpm | — | — |
| Tub filler | 4 gpm | — | — |
Incoming Water Temperature
The DOE assumes 50 °F unless you know better. Rinnai's ground water map gives these ranges for the coldest part of the year:
- 37–47 °F: upper Midwest, northern New England, Mountain West.
- 47–57 °F: Mid-Atlantic, Ohio Valley, central Plains.
- 57–67 °F: Southeast, lower Plains, southwest interior.
- 67–77 °F: Gulf Coast, south Texas, Florida.
Every 10 °F colder water adds about 14% to the load at 120 °F: two showers and a faucet need 166,000 BTU/h of gas with 57 °F water and 218,000 with 37 °F water.
Sizes by Household and Bathrooms
Navien's rule of thumb is 3.5 gpm for one or two fixtures at once, 5 gpm for two or three, and 7 gpm for three or four. In practice that means:
- One bathroom, or one or two people: a shower and a faucet, 3 gpm: 111,000 BTU/h of gas with 50 °F water.
- Two bathrooms, a family of four: two showers and a faucet, 5 gpm: 184,000 BTU/h.
- Three bathrooms, five or six people: three showers, 6 gpm: 221,000 BTU/h, more than a 199,000 BTU/h unit delivers at a 70 °F rise.
How much each size delivers at a 70 °F rise, condensing gas and electric:
Electric Tankless: kW, Amps and Breakers
Electric units need a lot of current: 51.2 kW for the default load is 214 A at 240 V. The largest common whole-house units are 36 kW and deliver about 3.5 gpm at a 70 °F rise. Stiebel Eltron's Tempra 36 takes three 50 A breakers and asks for 300 A house service; the Tempra 24 takes two and 150 A service.
Size the circuit wiring and convert between kW and BTU/h. A gas unit needs a gas line sized for its full input over the length of the run, by its installation manual and the local fuel gas code.
Tankless or Tank?
A gas tankless heater costs about $5,800 installed against about $2,660 for a tank heater. Price the whole plumbing job, with the old heater out and the new lines in. The hot water lines have to carry the flow too: 5 gpm runs at 4.5 ft/s in ¾ in PEX, under the 5 ft/s hot water limit the pipe velocity calculator checks.
Frequently Asked Questions
What size tankless water heater do I need?
Add the flow of the fixtures that run at once and multiply by the temperature rise and 500. Two showers and a bathroom faucet, 5 gpm, heated from 50 °F to 120 °F need 175,000 BTU/h of heat, about 184,000 BTU/h of gas input in a condensing unit.
What size tankless water heater for a family of 4?
Usually enough for two showers at once plus a faucet, about 5 gpm: 184,000 BTU/h of gas input with 50 °F incoming water and about 211,000 with 40 °F water. Electric units of 27 to 36 kW cover two showers only where the incoming water is warm.
How many gpm do I need for 2 bathrooms?
About 4 to 5 gpm of hot water: two showers at 2 gpm of hot each, plus a faucet. Showerheads may use up to 2.5 gpm under federal rules, 2.0 for WaterSense models, and part of that is cold water mixed in.
What size tankless water heater for one bathroom?
A shower and a faucet at once, about 3 gpm of hot water: 111,000 BTU/h of gas input with 50 °F incoming water, or 30.7 kW electric.
How many gpm does a shower need from a tankless heater?
About 2 gpm of hot water. A WaterSense showerhead uses up to 2.0 gpm and a standard one up to 2.5, and at a 120 °F setting part of that is cold water mixed in at the valve.
What size electric tankless water heater do I need?
kW = gpm × rise ÷ 6.83. Two showers and a faucet at a 70 °F rise need 51 kW, more than the largest common whole-house units of 36 kW, which deliver about 3.5 gpm at that rise. Such a unit draws 150 A at 240 V and its maker asks for 300 A service.
What size breaker does an electric tankless water heater need?
The one in the maker's instructions, usually several double-pole breakers. Stiebel Eltron's 36 kW Tempra takes three 50 A breakers and three 8 AWG circuits; its 24 kW model takes two.
What temperature rise should I use?
The coldest incoming water of the year subtracted from the hot water temperature. The DOE assumes 50 °F in and 120 °F out, a 70 °F rise; Rinnai’s ground water map runs from about 37 °F in the far north to 77 °F in south Florida.
How much does a tankless water heater cost?
About $5,800 installed for a gas unit, more when the gas line or venting has to change. A 27 kW electric unit costs about $607 before installation and the electrical work.
Is a tankless water heater cheaper than a tank?
Not to install: about $5,800 for a gas tankless unit against about $2,660 for a tank heater, installed. What you get for it is hot water for as long as the fixtures stay within its flow.
Sources
- Energy conservation standards and their compliance dates, 10 C.F.R. § 430.32 (2026).
- Navien. (2024, September 13). Tankless water heater sizing guide.
- Rinnai America Corporation. (2022). North America ground water temperature map.
- Stiebel Eltron. (2025). Tempra series technical specifications.
- U.S. Department of Energy. (n.d.). Sizing a new water heater. Energy Saver.
- U.S. Environmental Protection Agency. (n.d.). WaterSense: Showerheads.
Updated .
Cite this page as: