ConstructionCalculators

Wire Size Calculator

Enter the breaker or the load, the voltage and the distance to get the wire gauge by NEC ampacity, checked for voltage drop over the run.

240 V50 A237.5 VLoad6 AWG copper50 ft one way
Circuit
A
ft

You need

6AWG

copper, NM-B cable, 13.3 mm²

Ampacity60 °C column, Table 310.16
55 A
Voltage dropat 50 A over 50 ft
1.0%
Longest runfor a 3% drop
146 ft
Aluminumsame circuit
4 AWG
$190

What Size Wire Do I Need?

A 50 A breaker at 240 V, 50 ft from the load, needs 6 AWG copper in NM-B cable. Its ampacity is 55 A, and the voltage drop over the run is 2.46 V, or 1.0%. The same wire can run 146 ft before the drop passes 3%.

Wire size by breaker, before voltage drop and derating:

BreakerCu NM-BCu 75 °CAl 75 °C
15 A141412
20 A121210
30 A10108
40 A888
50 A686
60 A464
70 A443
80 A242
100 A—31
125 A—12/0
150 A—1/03/0
200 A—3/0250 kcmil

The 75 °C columns apply to THHN wire when the breaker and the equipment are marked for 75 °C, and to every circuit over 100 A. NM-B is made from 14 to 2 AWG in even sizes, so a 70 A circuit takes 4/3 and an 80 or 90 A circuit 2/3; past 95 A you need THHN in conduit or another cable.

Gauge numbers run backward: the smaller the number, the thicker the wire. Copper conductors to scale:

1412108642
Copper 14 to 2 AWG, drawn to scale by area

Each step of three gauge numbers doubles the copper. 6 AWG has four times the area of 12 AWG, 26,240 circular mils against 6,530, and 4/0 has about eight times the area of 6 AWG.

Wire Gauge Ampacity Chart

NEC Table 310.16 gives the current each wire may carry, for up to three current-carrying wires in a cable or conduit at 86 °F (30 °C):

SizeCu 60 °CCu 75 °CAl 75 °C
1415 A20 A—
1220 A25 A20 A
1030 A35 A30 A
840 A50 A40 A
655 A65 A50 A
470 A85 A65 A
385 A100 A75 A
295 A115 A90 A
1110 A130 A100 A
1/0125 A150 A120 A
2/0145 A175 A135 A
3/0165 A200 A155 A
4/0195 A230 A180 A
250 kcmil215 A255 A205 A
300 kcmil240 A285 A230 A
350 kcmil260 A310 A250 A
400 kcmil280 A335 A270 A
500 kcmil320 A380 A310 A

The 60 °C column covers NM-B, UF and TW wire; 75 °C covers THW, THWN, XHHW and SE cable; 90 °C covers THHN, THWN-2 and XHHW-2. These values are the same in the 2017, 2020 and 2023 editions of the NEC.

Wire Size in Inches and mm²

Gauge sizes stand for an area. Circular mils are the area of a round wire measured in thousandths of an inch, so a solid wire's diameter in mils is the square root of its circular mils:

SizeCircular milsmm²Solid diameter
14 AWG4,1102.080.064 in
12 AWG6,5303.310.081 in
10 AWG10,3805.260.102 in
8 AWG16,5108.370.128 in
6 AWG26,24013.30.162 in
4 AWG41,74021.20.204 in
2 AWG66,36033.60.258 in
1/0 AWG105,60053.50.325 in
2/0 AWG133,10067.40.365 in
4/0 AWG211,6001070.460 in

Building wire from 8 AWG up is stranded, and strands leave gaps, so it measures a little more across: 0.146 in for stranded 8 AWG against 0.128 in solid. Outside the US, cable is sold by mm²: 6 AWG at 13.3 mm² sits between the 10 and 16 mm² metric sizes.

Which Column Applies

The column is set by the weakest part of the circuit, usually the breaker and device terminals, not by the wire's insulation:

  • NM-B and UF cable: 60 °C, even though the wires inside are rated 90 °C (NEC 334.80).
  • Circuits of 100 A or less: 60 °C, unless the breaker and the equipment are marked for 75 °C (110.14(C)(1)(a)).
  • Over 100 A: 75 °C (110.14(C)(1)(b)).
  • 90 °C: only the starting point when derating for heat or for more than three current-carrying wires together; the result still may not exceed the terminal column.

Small wires have their own limit. Whatever the table says, NEC 240.4(D) allows 14 AWG copper on a 15 A breaker at most, 12 AWG copper on 20 A, 10 AWG copper on 30 A, 12 AWG aluminum on 15 A and 10 AWG aluminum on 25 A.

The calculator sizes the wire for the full breaker rating. NEC 240.4(B) does let a wire whose ampacity falls between standard breaker sizes go on the next size up, such as 6 AWG NM-B (55 A) on a 60 A breaker, as long as the load itself stays within 55 A and the circuit doesn't feed several receptacles. It never applies to the small wires above.

How to Calculate Wire Size for Amps and Distance

  1. 1Find the current the wire must carry: the breaker rating, or 125% of a load that runs 3 hours or more.
  2. 2Pick the column: 60 °C for NM-B and for most circuits up to 100 A, 75 °C when the terminals are marked for it or the circuit is over 100 A.
  3. 3Take the smallest size whose ampacity meets the current, within the 240.4(D) limits for 14, 12 and 10 AWG.
  4. 4Measure the one-way distance from the panel to the load along the route the cable will take, not in a straight line.
  5. 5Check the voltage drop over that distance. If it passes 3%, go up a size and check again.

The voltage drop is the current times the resistance of both conductors, the one going out and the one coming back:

Voltage drop = 2 × R × I × L ÷ 1,000R = 0.491 ohms per 1,000 ft for 6 AWG copper (NEC Chapter 9, Table 8)2 × 0.491 × 50 A × 50 ft ÷ 1,000 = 2.46 V2.46 V ÷ 240 V = 1.0%

L is the one-way distance; the 2 counts the wire out and back. Three-phase circuits use 1.732 in place of 2. The NEC recommends no more than a 3% drop on a branch circuit and 5% in total with the feeder.

To go straight to the size, turn the formula around. A 3% drop at 240 V is 7.2 V, so the wire may have at most 7.2 × 1,000 ÷ (2 × 50 A × 50 ft) = 1.44 ohms per 1,000 ft. 10 AWG copper, at 1.24, would pass on drop alone, but the 50 A ampacity still calls for 6 AWG. Short runs are sized by ampacity, long runs by drop. Look up the resistance of any size and length.

Wire Size by Distance

Copper wire for common circuits at the full breaker current and a 3% drop, NM-B up to 60 A and THHN at 75 °C above:

Circuit50 ft100 ft200 ft
20 A, 120 V1084
30 A, 240 V1086
40 A, 240 V884
50 A, 240 V664
60 A, 240 V442
100 A, 240 V331
200 A, 240 V3/03/03/0

A 50 A circuit at 150 ft shows how the drop takes over. 6 AWG would lose 7.37 V there, 3.1%, so the size goes up to 4 AWG, which delivers 235.4 V at the far end:

240 V50 A235.4 VLoad4 AWG copper150 ft one way
50 A at 240 V, 150 ft one way: 4 AWG copper, 1.9% drop

How far the smallest copper NM-B for each breaker can run before the drop passes 3%, at the full breaker current:

120 V240 V
15 A, 14 AWG
38 ft
76 ft
20 A, 12 AWG
45 ft
90 ft
30 A, 10 AWG
48 ft
96 ft
40 A, 8 AWG
57 ft
115 ft
50 A, 6 AWG
73 ft
146 ft
60 A, 4 AWG
97 ft
194 ft
120 V, 240 V, in feet

Most circuits carry less than their breaker rating, so the real drop is usually smaller. For a known load, switch the calculator to Load in Amps: the wire is still sized for the breaker, but the drop is figured at the current that actually flows.

Continuous Loads, EV Chargers and Appliances

A load that runs at full current for 3 hours or more is continuous, and the wire and breaker must be rated for 125% of it (NEC 210.19(A)(1) and 210.20(A)). Choose Load in Amps and set Runs 3+ hours to Yes to add it.

  • EV charger: always continuous (625.42). A 32 A charger needs a 40 A circuit and 8 AWG copper; 40 A needs 50 A and 6 AWG; 48 A needs 60 A and 4 AWG copper NM-B, or 6 AWG THHN at 75 °C.
  • Electric dryer: most use a 30 A circuit and 10/3 cable, two hots, a neutral and the ground; the nameplate rules.
  • Electric range: 8¾ kW or more needs at least a 40 A circuit (210.19(C)); 40 A takes 8/3 NM-B, 50 A takes 6/3.
  • Air conditioner or heat pump: enter the Minimum Circuit Ampacity (MCA) from the nameplate as the load, with Runs 3+ hours set to No, since the MCA already includes the extra; the breaker is the nameplate's maximum (MOCP). To size the unit itself, work out the AC size.
  • Electric tankless water heater: whole-house models draw 100 A or more, split over two or three 40 or 50 A circuits, each sized on its own. Find the kilowatts you need for a tankless heater.

Count the wires as well as their size. A 240 V load with no 120 V parts, like a water heater, needs two hots and the ground: /2 cable. A range, dryer or 14-50 outlet also needs a neutral: /3 cable.

Service and Subpanel Feeders

A 120/240 V service or feeder of 100 to 400 A that carries the entire load of a house or apartment may be sized at 83% of its rating (NEC 310.12):

ServiceCopperAluminum
100 A4 AWG2 AWG
125 A2 AWG1/0 AWG
150 A1 AWG2/0 AWG
200 A2/0 AWG4/0 AWG
400 A400 kcmil600 kcmil

A subpanel that feeds only part of the house does not get the 83% rule. Size it by Table 310.16 like any circuit: a 100 A subpanel with 75 °C terminals needs 3 AWG copper or 1 AWG aluminum. At 240 V and the full 100 A, copper goes to 2 AWG at 150 ft, 1 AWG at 200 ft and 2/0 at 300 ft to stay under a 3% drop. Feeders to a detached garage or shop are often run in conduit; find the conduit size for the wires.

Copper vs. Aluminum Wire

Aluminum carries less current than copper of the same size, so it runs one or two sizes larger: 6 AWG copper NM-B carries a 50 A circuit, where aluminum needs 4 AWG at 60 °C or 6 AWG at 75 °C. Size for size, its resistance is about 1.64 times that of copper, so over a long run it loses more voltage as well.

Today aluminum is used mostly for feeders and services, where its lower price adds up: 4/0 aluminum, the usual 200 A service wire, costs about $1.32 a foot against $4.29 for the 2/0 copper that does the same job. It needs terminals marked AL/CU or CO/ALR and an antioxidant paste where the maker calls for it. Table 310.16 starts aluminum at 12 AWG; there is no 14 AWG aluminum building wire.

Derating for Heat and Bundled Wires

Table 310.16 assumes 86 °F around the wire and no more than three current-carrying wires together. Hotter air or more wires in one conduit lower the ampacity, and the calculator doesn't include either. Start from the 90 °C column for THHN and multiply:

ConditionFactor, 90 °C wireFactor, 75 °C wire
Ambient 87–95 °F0.960.94
Ambient 96–104 °F0.910.88
Ambient 105–113 °F0.870.82
4–6 current-carrying wires0.800.80
7–9 current-carrying wires0.700.70
10–20 current-carrying wires0.500.50

Nine 12 AWG THHN in one conduit at 86 °F keep 30 A × 0.70 = 21 A each, still enough for 20 A breakers. Run the same conduit through a 104 °F space and it drops to 30 × 0.91 × 0.70 = 19.1 A, so the circuits need 10 AWG. The ambient factors come from NEC Table 310.15(B)(1), the wire counts from 310.15(C)(1); a ground wire and a neutral that carries only the unbalanced current don't count.

What Wire Costs

Wire is priced by the foot and follows the price of copper. Typical prices for NM-B cable with a ground and for single conductors:

SizeNM-B /3THHNAluminum
14 AWG$0.59$0.16—
12 AWG$0.85$0.24$0.22
10 AWG$1.30$0.36$0.24
8 AWG$2.50$0.56$0.27
6 AWG$3.80$0.87$0.32
4 AWG$7.60$1.37$0.41
2 AWG$14.00$2.15$0.54

The default circuit takes 50 ft of 6/3 NM-B at $3.80 a foot, $190. Pick /2 or /3, or the number of THHN conductors, in the last row of the calculator, and click the price to change it.

  • Buy a little extra. The run rarely goes in a straight line, and NEC 300.14 wants at least 6 in of free wire at every box.
  • Count conductors for THHN. Each hot, the neutral and the ground are separate wires. The ground may be smaller: a 50 or 60 A circuit takes a 10 AWG copper ground (NEC Table 250.122).
  • Large NM-B costs more than it looks. 4/3 and 2/3 are specialty cables, priced well above the copper they hold; THHN in conduit is often cheaper for a long feeder.

Frequently Asked Questions

What size wire do I need for a 50 amp breaker?

6 AWG copper in NM-B cable, or 8 AWG copper THHN when the breaker and the equipment are marked for 75 °C. In aluminum it is 6 AWG at 75 °C. At 240 V, 6 AWG copper keeps the voltage drop under 3% up to 146 ft at the full 50 A; at 150 ft it takes 4 AWG.

What size wire do I need for 30 amps?

10 AWG copper, the largest breaker the NEC allows on 10 AWG, or 8 AWG aluminum. At 120 V and the full 30 A, 10 AWG stays under a 3% drop only to about 48 ft; for 100 ft use 6 AWG.

Can I use 12 gauge wire on a 15 amp circuit?

Yes. A bigger wire on a smaller breaker is allowed, because the breaker protects the wire. The reverse is not: 14 AWG copper may not go on a 20 A breaker (NEC 240.4(D)).

Is 10 gauge wire good for 40 amps?

No. Table 310.16 lists 10 AWG copper at 30 to 40 A, but NEC 240.4(D) limits it to a 30 A breaker. A 40 A circuit needs 8 AWG copper.

What is the amp rating of 6/3 wire?

55 A. Copper NM-B cable is held to the 60 °C column (NEC 334.80), and 6 AWG is 55 A there. The same 6 AWG as THHN on 75 °C terminals is 65 A.

What size wire do I need for a 100 amp subpanel?

3 AWG copper or 1 AWG aluminum THHN or XHHW when the panel and breaker terminals are marked for 75 °C. NM-B can’t do it: the largest, 2/3, is good for 95 A. At 240 V and the full 100 A, 3 AWG copper passes a 3% drop to 146 ft; use 2 AWG at 150 ft and 1 AWG at 200 ft.

What size wire do I need for 200 amp service?

For a service or feeder that carries the whole house, NEC 310.12 lets it be sized at 83%: 2/0 copper or 4/0 aluminum. Any other 200 A feeder uses Table 310.16 at 75 °C: 3/0 copper or 250 kcmil aluminum.

What size wire do I need for an EV charger?

EV charging counts as a continuous load (NEC 625.42), so the circuit is 125% of the charger current. A 48 A charger needs a 60 A circuit with 4 AWG copper NM-B or 6 AWG THHN at 75 °C; a 40 A charger needs 50 A and 6 AWG; a 32 A charger needs 40 A and 8 AWG.

What size wire do I need for a hot tub?

The size for the GFCI breaker on the nameplate, usually 40 to 60 A at 240 V: 8 AWG copper for 40 A, 6 AWG for 50 A, and 4 AWG NM-B or 6 AWG THHN for 60 A. Check the run for voltage drop, since spas often sit far from the panel.

How far can I run 12 gauge wire on a 20 amp circuit?

About 45 ft at 120 V with the full 20 A flowing, for a 3% voltage drop, or 56 ft at a 16 A load. At 240 V the distances double.

Does voltage change the wire size?

Not the ampacity: 30 A needs 10 AWG copper at 120 V and at 240 V. It changes the voltage drop: the same current loses the same volts, which is half the percentage at 240 V, so a 240 V circuit can run twice as far.

How much voltage drop is allowed?

The NEC recommends no more than 3% on a branch circuit and 5% in total with the feeder. That is an informational note, not a rule, but equipment instructions may require a minimum voltage at the unit.

What size wire do I need for 12 V DC?

Low voltage loses a large share to drop. A 10 A load 20 ft from a 12 V battery needs 8 AWG copper to stay under 3%, although 14 AWG carries the current.

How much does wire cost per foot?

About $0.50 a foot for 14/2 NM-B, $0.72 for 12/2, $1.30 for 10/3 and $3.80 for 6/3. Single THHN copper conductors run about $0.24 a foot in 12 AWG and $0.87 in 6 AWG.

Sources

  • Cerrowire. (2021). Ampacity charts.
  • International Association of Electrical Inspectors. (2017, April 5). Voltage drop formulas. IAEI Magazine.
  • Michigan State University, Biosystems and Agricultural Engineering Department. (2024). Electrical tech note 227: Sizing conductors to minimize voltage drop.
  • National Fire Protection Association. (2022). NFPA 70: National electrical code (2023 ed.).
  • National Fire Protection Association. (2024). NEC Code-Making Panel 6 first draft report (NFPA 70, 2025 annual revision cycle).
  • Pauley, J. (2000, March 16). Wire temperature ratings and terminations. IAEI Magazine.
  • Southwire Company. (n.d.). Romex brand SIMpull type NM-B cable (SPEC 10028) [Specification sheet].

Updated .