Wire Resistance Calculator

Choose the wire size and metal and enter the length and temperature to get the resistance in ohms, with the voltage drop and power lost at a current.

100 ft0.198 Ω12 AWG
Wire
ft
°F
A

Resistance

0.198Ω

12 AWG copper, 100 ft at 167 °F

Per 1,000 ftat this temperature
1.98 Ω
Out and backtwo conductors, a circuit this long
0.396 Ω
Voltage dropat 16 A, out and back
6.34 V
Power lostin the wire as heat
101.4 W
Area6,530 circular mils
3.31 mm²

Wire Resistance Chart

100 ft of 12 AWG copper at 75 °C has 0.198 ohms. A circuit that long has two conductors, 0.396 ohms, so 16 A through it drops 6.34 V and heats the wire with 101 W.

Resistance in ohms per 1,000 ft, copper and aluminum:

SizeCu 75 °CCu 20 °CAl 75 °C
24 AWG31.225.751.2
22 AWG19.616.232.3
20 AWG12.310.120.3
18 AWG7.776.3912.8
16 AWG4.884.018.01
14 AWG3.142.585.17
12 AWG1.981.633.25
10 AWG1.241.022.04
8 AWG0.7780.6401.28
6 AWG0.4910.4040.808
4 AWG0.3080.2530.508
3 AWG0.2450.2010.403
2 AWG0.1940.1600.319
1 AWG0.1540.1270.253
1/0 AWG0.1220.1000.201
2/0 AWG0.09670.07950.159
3/0 AWG0.07660.06300.126
4/0 AWG0.06080.05000.100
250 kcmil0.05150.04240.0847
300 kcmil0.04290.03530.0707
350 kcmil0.03670.03020.0605
400 kcmil0.03210.02640.0529
500 kcmil0.02580.02120.0424

From 14 AWG up, the values are NEC Chapter 9 Table 8 for stranded, uncoated conductors, the figures electricians use for voltage drop. The 24 to 16 AWG rows are solid wire, worked out from the AWG diameters and the resistivity of standard annealed copper. Divide by 1,000 for ohms per foot, or multiply by 3.281 for ohms per kilometer.

Resistance and Temperature

Metal resists more as it warms. The note to Table 8 adjusts the 75 °C values with α = 0.00323 per °C for copper and 0.00330 for aluminum. For copper that is the same rate as the 0.00393 per °C of NBS Handbook 100, which is figured from 20 °C. 12 AWG copper, ohms per 1,000 ft:

32 °F (0 °C)
1.50 Ω
68 °F (20 °C)
1.63 Ω
122 °F (50 °C)
1.82 Ω
167 °F (75 °C)
1.98 Ω
194 °F (90 °C)
2.08 Ω
12 AWG copper, in ohms per 1,000 ft

Use 75 °C for wire carrying its full current in a wall or conduit, as the NEC does for voltage drop, and 20 °C for a bench test or a cool, lightly loaded run. A wire at 90 °C, the limit of THHN insulation, has about 5% more resistance than the table shows.

How to Calculate Wire Resistance

  1. 1Find the resistance per 1,000 ft for the size and metal in the chart.
  2. 2Multiply it by the length in feet and divide by 1,000.
  3. 3For a circuit, double the one-way length: the current goes out on one wire and back on the other.
  4. 4Correct for temperature if the wire runs hotter or cooler than 75 °C.
R = ohms per 1,000 ft × length ÷ 1,000 × [1 + α × (T − 75 °C)]1.98 × 100 ÷ 1,000 = 0.198 Ω16 A × 0.198 Ω × 2 = 6.34 V; 16² × 0.396 = 101 W

The default circuit, one conductor out and one back:

0.198 Ω0.198 Ω16 ALoad100 ft one way

Without a table, use R = ρ × L ÷ A. Copper's resistivity at 20 °C is 10.371 ohm-circular mils per foot, so 100 ft of 12 AWG, 6,530 circular mils, has 10.371 × 100 ÷ 6,530 = 0.159 ohms. The chart's 1.63 ohms per 1,000 ft at 20 °C is a little higher because the strands of stranded wire spiral around each other, so each one is slightly longer than the wire.

Low-Voltage and Metric Wire

Resistance matters most at low voltage, where a few volts lost is a large share. A 12 V light drawing 5 A at the end of 50 ft of 16 AWG copper sees 0.40 ohms out and back at 20 °C, a 2.0 V drop: 17% of the supply. The same run at 120 V would lose under 2%.

Metric cable is sized by area. At 20 °C, copper's resistance is 0.017241 ohms for each meter of 1 mm² wire, so divide by the area: 2.5 mm² copper has 0.017241 × 1,000 ÷ 2.5 = 6.9 ohms per km. That size sits between 14 and 12 AWG; switch the calculator to Metric for lengths in meters and results per km.

What Changes the Resistance

  • Size: every three gauge numbers double the area and halve the resistance. 6 AWG has four times the copper of 12 AWG and a quarter of the resistance, 0.491 ohms per 1,000 ft against 1.98.
  • Metal: aluminum conductor has 61% of copper's conductivity, so the same size has about 1.64 times the resistance.
  • Length: resistance grows in step with length; twice the run, twice the ohms and twice the voltage drop.
  • Solid or stranded: stranded wire has about 2 to 3% more resistance than solid of the same gauge.

On a circuit, resistance turns into voltage drop and heat. Find the gauge that keeps the drop under 3% at your current and distance. For long low-voltage runs to LEDs, count the wire's drop before you pick the LED resistor, and for conductors in conduit, check the conduit fill.

Frequently Asked Questions

What is the resistance of 12 gauge copper wire?

1.98 ohms per 1,000 ft for stranded copper at 75 °C (NEC Chapter 9 Table 8), so 0.198 ohms in 100 ft. At room temperature, 20 °C (68 °F), it is about 1.63 ohms per 1,000 ft.

How do I calculate wire resistance?

Multiply the resistance per 1,000 ft for the size by the length and divide by 1,000. For a circuit, count both conductors: a 100 ft run of 12 AWG copper is 200 ft of wire, 0.396 ohms.

What is the formula for wire resistance?

R = ρ × L ÷ A: resistivity times length divided by area. For copper at 20 °C, ρ is 10.371 ohm-circular mils per foot, so 100 ft of 12 AWG (6,530 circular mils) has 10.371 × 100 ÷ 6,530 = 0.159 ohms.

What is the resistance of 22 gauge wire per foot?

About 0.0196 ohms per foot for solid copper at 75 °C, or 0.0162 at 20 °C (68 °F): 16.2 ohms per 1,000 ft.

How does temperature change wire resistance?

Resistance rises with temperature. The note to NEC Table 8 gives R2 = R1 × [1 + α × (T2 − 75)], with α 0.00323 for copper and 0.00330 for aluminum. Copper at 20 °C has about 18% less resistance than the 75 °C table value.

Is aluminum wire resistance higher than copper?

Yes, about 64% higher for the same size: 12 AWG aluminum is 3.25 ohms per 1,000 ft against 1.98 for copper. That is why aluminum runs one or two sizes larger for the same current.

How much voltage drop does wire resistance cause?

Voltage drop is current times the resistance of both conductors. 16 A through 100 ft of 12 AWG copper, out and back, loses 6.34 V, 5.3% of 120 V, and turns 101 W into heat in the wire.

What is the resistance of wire per foot?

Divide the Table 8 value by 1,000: 14 AWG copper is 0.00314 ohms per foot, 12 AWG 0.00198, 10 AWG 0.00124 at 75 °C.

What is the resistance of wire per meter?

Multiply the value per 1,000 ft by 3.281 for ohms per kilometer, then divide by 1,000 for ohms per meter. 12 AWG copper at 75 °C is 6.50 ohms per km, 0.0065 ohms per meter.

How do I measure wire resistance with a multimeter?

Set the meter to its lowest ohms range, touch the probes together and note that reading, then measure across the two ends of the wire and subtract it. Short lengths of building wire read only tenths of an ohm, close to what the meter can resolve.

Sources

  • Michigan State University, Biosystems and Agricultural Engineering. (2024). Electrical tech note 227: Sizing conductors to minimize voltage drop.
  • National Bureau of Standards. (1966). Copper wire tables (Handbook 100). U.S. Department of Commerce.
  • National Fire Protection Association. (2022). NFPA 70: National electrical code (2023 ed., Chapter 9, Table 8).
  • Southwire Company. (n.d.). Overhead conductor comparison [Product sheet].

Updated .

Cite this page as:

Daniel, P. Wire Resistance Calculator. Available at: https://constructioncalculators.com/wire-resistance-calculator/. Accessed: October 28, 2026.