HVAC Calculator

Enter your house's size, insulation, windows, location and bedrooms to size the furnace, air conditioner, airflow and fresh-air ventilation.

2,000 sq ft
House
sq ft
ft
sq ft

System

4 tons

cooling · 40,000 BTU/h furnace

Heat lossChicago, IL, 2°F design
38,295 BTU/h
Furnace38,400 BTU/h output at 96% AFUE
40k input
Air conditioner2,000 sq ft at 500 sq ft a ton
4 tons
Airflow400 cfm a ton
1,600 cfm
Fresh airIRC continuous; ASHRAE 62.2: 90 cfm
60 cfm
Furnace and AC, installed
$14,600

What Size HVAC System Do I Need?

A two-story, 2,000 square foot older house in Chicago loses about 38,295 BTU per hour on a 2°F design day, so a 96% furnace with 40,000 BTU of input covers it. At 500 square feet a ton it takes a 4 ton air conditioner, moving about 1,600 cfm, and 60 cfm of continuous fresh air under the IRC. Furnace and air conditioner come to about $14,600 installed.

The four parts of the system, each sized from the house:

1234
  1. 1Furnace: 40,000 BTU input, 38,400 out at 96%
  2. 2Air conditioner: 4 tons, outside
  3. 3Supply ducts: about 1,600 cfm
  4. 4Fresh air: 60 cfm, continuous

How to Size an HVAC System

Size the heating from the heat loss, the cooling from the floor area or a load calculation, and the airflow and fresh air from those:

Cooling tons = floor area ÷ sq ft a ton; airflow = tons × 400 cfm2,000 ÷ 500 = 4 tons; 4 × 400 = 1,600 cfmFurnace: 40,000 × 0.96 = 38,400 BTU/h ≥ 38,295 heat loss$4,600 + 4 × $2,500 = $14,600

The heat loss is the sum of what leaks through the walls, windows, ceiling and floor, plus the air that leaks in, each worked out at the design temperature for your area; break the heat loss down part by part. ENERGY STAR allows a furnace output of 100% to 140% of that loss, so the calculator picks the smallest standard furnace that covers it. For one room, work out the BTUs for that room.

Building codes require equipment sized by an ACCA Manual J load calculation and Manual S selection (IRC M1401.3, IECC R403.7). The calculator is the estimate before that, good for budgeting and for checking a contractor's proposal.

HVAC Size by Climate

The heating side depends on how cold it gets. ENERGY STAR lists a 99% heating design temperature for every county, the cold the house has to hold 70°F against. The same older 2,000 square foot house, heat loss at each area's design temperature:

Minneapolis
43,927 BTU/h
Chicago
38,295 BTU/h
Boston
32,664 BTU/h
Atlanta
25,343 BTU/h
Seattle
24,216 BTU/h
Houston
20,837 BTU/h
Miami
12,390 BTU/h
Heat loss, BTU per hour, in BTU per hour
AreaDesign tempFurnace inputHeat pump
Minneapolis, MN-8°F60,000 BTU5 tons
Chicago, IL2°F40,000 BTU5 tons
Boston, MA12°F40,000 BTU4 tons
Atlanta, GA25°F40,000 BTU3 tons
Seattle, WA27°F40,000 BTU2.5 tons
Houston, TX33°F40,000 BTU2 tons
Miami, FL48°F40,000 BTU1.5 tons

Furnaces at 96% AFUE in 20,000 BTU steps; heat pumps sized to carry the load at the design temperature, where they lose capacity. A house built to the current energy code loses far less: in Chicago, about 22,669 BTU an hour with code insulation, low-e windows and tight construction, against 38,295 for the older house.

AC Tons by House Size

House500 sq ft a ton400 sq ft a ton900 sq ft a ton
1,000 sq ft2 tons2.5 tons1.5 tons
1,200 sq ft2.5 tons3 tons1.5 tons
1,500 sq ft3 tons4 tons2 tons
1,800 sq ft4 tons5 tons2 tons
2,000 sq ft4 tons5 tons2.5 tons
2,200 sq ft5 tons5.5 tons2.5 tons
2,500 sq ft5 tons6.5 tons3 tons
3,000 sq ftnull tons7.5 tons3.5 tons

The 400 to 500 square feet a ton is the common estimate; 900 is the middle of DOE's 800 to 1,000 for a very efficient house. DOE calls the common estimate a rule that ignores climate and efficiency. Sizes are rounded up to the standard sizes, 1.5 to 5 tons in half tons with no 4.5, and to the next half ton above 5.

Tons, BTU and Kilowatts

A ton of cooling is 12,000 BTU per hour, about 3.5 kW. Most makers write the nominal size into the model number in thousands of BTU, so a 3 ton condenser carries 036 or 36:

SizeBTU per hourKilowattsModel code
1.5 tons18,0005.3018
2 tons24,0007.0024
2.5 tons30,0008.8030
3 tons36,00010.6036
3.5 tons42,00012.3042
4 tons48,00014.1048
5 tons60,00017.6060

The code is the nominal size; the rated output on the spec sheet is often a little different. Check the maker's nomenclature for the exact model line before relying on it.

Airflow and Fresh Air

  • Airflow: the blower and ducts carry about 400 cfm per ton; ACCA notes about 350 suits hot, humid climates and up to 450 dry ones. Size the ducts for that airflow.
  • Fresh air: the IRC table gives 60 cfm of continuous ventilation for 1,501 to 3,000 square feet with 2 or 3 bedrooms; ASHRAE 62.2 gives 90 for the default house. The CFM Calculator works out a single room's air.

Duct Size for the System

A bigger system moves more air, and the supply trunk has to carry all of it. At 400 cfm a ton, the round smooth metal duct that carries the whole airflow at a friction rate of 0.08 inch of water per 100 feet:

SystemAirflowRound trunk
2 tons800 cfm14 in
2.5 tons1,000 cfm16 in
3 tons1,200 cfm16 in
3.5 tons1,400 cfm18 in
4 tons1,600 cfm18 in
5 tons2,000 cfm20 in

A rectangular trunk of the same capacity, or two smaller round trunks, carries the same air, and each branch takes its share of the airflow by the room's load. Replacing equipment with a larger size on the old ducts raises the friction and the noise, so check the ducts when the tonnage changes.

What an HVAC System Costs

The calculator prices a gas furnace at about $4,600 installed, central air at $2,500 a ton and a heat pump at $4,500 a ton, each editable. The default house comes to about $14,600 for a furnace and a 4 ton air conditioner; a heat pump in place of both, sized to carry the house on Chicago's 2°F design day, is 5 tons, about $22,500. Size the heating as a furnace in BTU or a heat pump in tons, and size the AC unit for cooling alone.

Frequently Asked Questions

What size HVAC system do I need for a 2,000 sq ft house?

About a 4 ton air conditioner at 500 square feet a ton, and in Chicago a 40,000 BTU furnace at 96% AFUE for an older house that loses 38,295 BTU per hour. The blower moves about 1,600 cfm.

How many square feet does a ton of AC cool?

The common estimate is one ton for each 400 to 500 square feet. DOE says that rule ignores climate and efficiency, and that one ton can cool 800 to 1,000 square feet of a very efficient house.

How much airflow does an HVAC system need?

About 400 cfm per ton of cooling. ACCA notes 350 cfm a ton suits hot, humid climates and 450 drier ones. A 4 ton system moves about 1,600 cfm.

How much fresh air does a house need?

The IRC requires continuous whole-house ventilation of 60 cfm for a house of 1,501 to 3,000 square feet with 2 or 3 bedrooms. ASHRAE 62.2 asks for 0.03 cfm per square foot plus 7.5 cfm per bedroom plus one: 90 cfm for 2,000 square feet and 3 bedrooms.

How are HVAC systems sized by code?

The IRC and IECC require equipment sized by ACCA Manual S from loads calculated by ACCA Manual J or another approved method.

What size HVAC system do I need by zip code?

The climate sets the heating side through the design temperature, the cold the system has to hold against. The same older 2,000 square foot house loses about 43,900 BTU an hour in Minneapolis at −8°F, 38,300 in Chicago at 2°F and 20,800 in Houston at 33°F. Pick your area in the calculator.

What size HVAC system do I need for a 1,500 sq ft house?

About 3 tons of cooling at 500 square feet a ton, or 2 tons for a very efficient house at 900. The furnace depends on the climate and insulation: run the house through the calculator with your area picked.

How much does a new HVAC system cost?

For the default 2,000 square foot house, about $14,600 installed: a $4,600 furnace and a 4 ton air conditioner at $2,500 a ton. A heat pump instead of both runs about $4,500 a ton. Every price in the calculator is editable.

Is it bad to oversize an HVAC system?

Yes. The Department of Energy warns that an oversized system costs more, gives poor comfort and can lead to mold, because the air conditioner shuts off before it dries the air. ENERGY STAR caps a single-speed air conditioner at 130% of the cooling load.

Sources

  • Akins, M. (2021, February 4). 400 CFM per ton, or is it? ACCA HVAC Blog.
  • ASHRAE. (2015). Addendum m to ANSI/ASHRAE Standard 62.2-2013: Ventilation and acceptable indoor air quality in low-rise residential buildings.
  • ENERGY STAR. (2018). Design temperature limit reference guide (Rev. 09/01/2018).
  • ENERGY STAR. (2025). National HVAC design supplement to Std. 310 for dwellings and units (Rev. 14).
  • Goodman Manufacturing. (2022). GSX14 split system air conditioner (SS-GSX14) [Specification sheet].
  • International Code Council. (2020). 2021 International Residential Code (Sections M1401.3 and M1505.4).
  • National Institute of Standards and Technology. (n.d.). NIST guide to the SI, Appendix B.9: Factors for units listed by kind of quantity.
  • Oregon Building Codes Division. (2021). Balanced mechanical whole-house ventilation strategies [Technical bulletin].
  • U.S. Department of Energy. (2021). Consumer guide to home heating and cooling (DOE/EE-2464).
  • Washington State Building Code Council. (n.d.). WAC 51-11R-40360, Section R403.7: Equipment sizing.

Updated .

Cite this page as:

Daniel, P. HVAC Calculator. Available at: https://constructioncalculators.com/hvac-calculator/. Accessed: October 28, 2026.