What Size Heat Pump Do I Need?
A two-story, 2,000 square foot older house loses about 38,295 BTU per hour in Chicago at its 2°F design temperature. A heat pump keeps about 68% of its rated capacity at 2°F, so it needs a rating of 56,436 BTU per hour, 4.7 tons: a 5 ton unit, which delivers about 40,714 BTU per hour at 2°F.
The share kept runs in a straight line from 100% at 47°F, where heat pumps are rated, to the 70% at 5°F that ENERGY STAR requires of cold-climate models. Your model's extended performance table gives its real figure.
Balance Point and Backup Heat
As it gets colder, the house loses more heat and the heat pump makes less. The two lines cross at the balance point. A 4 ton unit on the default Chicago house:
Below the balance point, electric strips or a furnace cover the shaded gap. NEEP allows a heat pump sized for 75% to 85% of the design load when backup heat is planned; sized for 100% to 115%, as the calculator does, it needs none. The 5 ton unit balances at about 0°F, below Chicago's 2°F design temperature.
Heat Pump Size by House and Climate
The same older 2,000 square foot house needs very different heat pumps by area. Rated capacity in tons, to carry the heating load at each design temperature:
| House | Houston, 33°F | Atlanta, 25°F | Chicago, 2°F |
|---|---|---|---|
| 1,000 sq ft | 1.5 | 2 | 3 |
| 1,500 sq ft | 2 | 2.5 | 5 |
| 2,000 sq ft | 2 | 3 | 5 |
| 2,500 sq ft | 2.5 | 3.5 | 5 + backup |
| 3,000 sq ft | 3 | 4 | 5 + backup |
Tons for older houses with R-11 walls, an R-19 attic, double-pane windows and average air leakage; one story under 1,800 square feet, two above. Standard sizes run 1.5 to 5 tons in half-ton steps, with no 4.5; “backup” means a 5 ton unit with supplemental heat.
Small Spaces and Mini-Splits
Central heat pumps start at 1.5 tons, more than an addition, a garage apartment or a single floor needs. Ductless mini-splits come smaller. The same sizing in Atlanta, at its 25°F design temperature, for one-story spaces:
| Space | Heat loss, BTU/h | Rated capacity | Mini-split |
|---|---|---|---|
| 400 sq ft | 7,058 | 8,374 | 9,000 BTU |
| 600 sq ft | 9,978 | 11,838 | 12,000 BTU |
| 900 sq ft | 14,220 | 16,872 | 18,000 BTU |
The rated capacity is at 47°F; it is larger than the heat loss because output falls in the cold. Check the maker's table for the model's output at your design temperature. For cooling a single room, size it by the ENERGY STAR room chart; heating a pool is a different job, so size the pool heater on its own.
Sizing Rules
- Heating load first: match 100–115% of the load at the design temperature, or 75–85% with backup heat (NEEP).
- No padding: NEEP warns against adding safety factors to the load.
- Cold-climate models: ENERGY STAR cold-climate units keep at least 70% of their capacity at 5°F, with a COP of at least 1.75 there.
To see where the heat goes, break down the house's heat loss; insulation and air sealing cut the load and with it the heat pump size.
Heat Pump or Furnace and Air Conditioner
A heat pump heats and cools with one outdoor unit. Sized for heating in a cold climate, it often has more cooling capacity than the house needs, which DOE notes; in a mild climate the cooling load may set the size instead. The calculator prices a heat pump at about $4,500 a ton installed, so the 5 tons for the default house come to about $22,500. A gas furnace and a separate air conditioner for the same house are priced as a full HVAC system, and the furnace alone with our furnace BTU calculator.
Efficiency is rated as SEER2 for cooling and HSPF2 for heating. From 2023 the federal minimum for a split heat pump is 14.3 SEER2 and 7.5 HSPF2; ENERGY STAR asks for at least 15.2 SEER2 and 7.8 HSPF2, and cold-climate models must keep 70% of their capacity at 5°F.
Frequently Asked Questions
What size heat pump do I need for a 2,000 sq ft house?
About 5 tons for a two-story, 2,000 square foot older house in Chicago, whose heat loss is 38,295 BTU per hour at 2°F, because a heat pump keeps only part of its capacity in the cold. In Atlanta, at 25°F, the same house needs 2.51 tons of rating, so a 3 ton unit.
How many square feet does a 3 ton heat pump cover?
It depends on the house and the climate more than on the area. A 3 ton heat pump rated at 36,000 BTU per hour that keeps 84% at Atlanta's 25°F delivers about 30,300 BTU per hour, enough for an older house of up to about 2,450 square feet there.
Why does a heat pump need to be bigger in cold climates?
Its heating capacity drops as the outdoor air gets colder. ENERGY STAR's cold-climate heat pumps must keep at least 70% of their 47°F capacity at 5°F; below the balance point, the temperature where capacity equals the load, backup heat makes up the rest.
Should a heat pump be sized for heating or cooling?
In cold climates, for heating; NEEP's guide says to match 100% to 115% of the heating load at the design temperature, or 75% to 85% with backup heat. A heat pump sized for heating may have more cooling capacity than the house needs, DOE notes.
What is a heat pump balance point?
The outdoor temperature where the heat pump's output equals the house's heat loss. Below it, backup heat makes up the difference. A 4 ton unit on the default Chicago house balances at about 8°F and needs about 5,724 BTU an hour of backup at 2°F.
What size heat pump do I need by zip code?
The climate decides it through the heating design temperature for your county. The same older 2,000 square foot house needs about 1.5 tons of heating capacity in Miami, 3 in Atlanta and over 5 in Minneapolis. Pick your area in the calculator.
How much does a heat pump cost?
The calculator uses about $4,500 a ton installed, editable: a 3 ton heat pump comes to about $13,500 and the 5 tons the default Chicago house needs to about $22,500.
What are SEER2 and HSPF2?
Seasonal cooling and heating efficiency ratings: BTU of cooling or heating per watt-hour over a season. From 2023 the federal minimum for a split heat pump is 14.3 SEER2 and 7.5 HSPF2; ENERGY STAR asks for at least 15.2 SEER2 and 7.8 HSPF2.
Sources
- ENERGY STAR. (n.d.). Heat pump equipment key product criteria.
- Northeast Energy Efficiency Partnerships. (2020). Guide to sizing & selecting air-source heat pumps in cold climates.
- Rudd, A. (2006). GM-0605: Design process for sizing. Building Science Corporation.
- U.S. Department of Energy. (2022). 2023 energy conservation standards for residential air conditioners and heat pumps: FAQ.
- U.S. Department of Energy, Building Science Education Solution Center. (n.d.). Cold climate heat pump sizing: Level 2 lecture notes and problem sets.
Updated .
Cite this page as:
Daniel, P. Heat Pump Size Calculator. Available at: https://constructioncalculators.com/heat-pump-size-calculator/. Accessed: October 28, 2026.