ConstructionCalculators

Heat Loss Calculator

Enter your house's floor area, insulation, windows and location to get its heat loss in BTU per hour on the coldest design day.

2,000 sq ft
House
sq ft
ft

Heat loss

38,295BTU/h

19.1 BTU/h per sq ft · 11.2 kW · ΔT 68°F

Walls1,724 sq ft
9,010 BTU/h
Windows300 sq ft, U 0.52
10,608 BTU/h
Ceiling1,000 sq ft
3,471 BTU/h
Floor1,000 sq ft
5,414 BTU/h
Air leakage133 cfm at 0.5 ACH
9,792 BTU/h

How Much Heat Does a House Lose?

A two-story, 2,000 square foot house with 8 ft ceilings, R-11 walls, an R-19 attic, double-pane windows and average air leakage loses about 38,295 BTU per hour in Chicago at its 2°F design temperature, 19.1 BTU per hour per square foot. The heat leaves five ways:

12345
  1. 1Walls: 9,010 BTU/h
  2. 2Windows: 10,608 BTU/h
  3. 3Ceiling: 3,471 BTU/h
  4. 4Floor: 5,414 BTU/h
  5. 5Air leakage: 9,792 BTU/h

Windows and air leakage are more than half of the loss here, though windows cover only 300 square feet, so they are where upgrades pay off first.

How to Calculate Heat Loss

For each surface, multiply its area by its U-factor and by the difference between 70°F indoors and the design temperature outdoors. Then add the air that leaks in, which has to be heated from outdoor temperature:

Heat loss = Σ U × A × ΔT + 1.08 × cfm × ΔTΔT = 70°F indoors − 2°F outdoors = 68°FWalls 9,010 + windows 10,608 + ceiling 3,471 + floor 5,414 = 28,503 BTU/hAir leakage: 16,000 cu ft × 0.5 ACH ÷ 60 = 133 cfm; 1.08 × 133 × 68 = 9,792 BTU/h28,503 + 9,792 = 38,295 BTU/h

The U-factor is the heat that passes through a square foot for each degree of difference, the inverse of the total R-value. The house is taken as a square footprint, half the floor area on each story, with windows equal to 15% of the floor area; enter your own story count, ceiling height and leakage to match. A furnace covering this loss needs about 39,891 BTU of input at 96%; pick the furnace size from there.

Older House or Built to Code

Built to the 2021 energy code, with low-e windows and tight construction, the same house loses about 22,669 BTU per hour, 41% less. Part by part:

Older houseBuilt to 2021 code
Walls
9,010
5,275
Windows
10,608
5,712
Ceiling
3,471
1,632
Floor
5,414
3,196
Air leakage
9,792
6,854
Older house, Built to 2021 code, in BTU per hour

One upgrade at a time on the older house, in BTU per hour saved on the design day:

UpgradeSaved, BTU/h
Low-e windows in place of clear double-pane4,896
Air sealing, 0.5 to 0.35 air changes an hour2,938
Attic insulation to code1,839
Wall insulation to code3,735

Every BTU per hour saved on the design day is a proportional cut in the heating bill over the season. Price the insulation, or figure blown-in insulation.

Design Temperatures

Location99% heatingΔT at 70°F1% cooling
Anchorage, AK-14°F84°F72°F
Phoenix area, AZ24°F46°F111°F
Los Angeles County, CA24°F46°F101°F
Denver, CO3°F67°F92°F
Miami, FL48°F22°F91°F
Atlanta, GA25°F45°F92°F
Chicago, IL2°F68°F91°F
Boston, MA12°F58°F88°F
Portland, ME2°F68°F84°F
Detroit, MI6°F64°F88°F
Minneapolis, MN-8°F78°F88°F
St. Louis County, MO2°F68°F94°F
Charlotte, NC25°F45°F92°F
Las Vegas area, NV17°F53°F111°F
New York, NY13°F57°F89°F
Columbus, OH9°F61°F90°F
Philadelphia, PA16°F54°F91°F
Nashville, TN18°F52°F92°F
Austin, TX30°F40°F98°F
Houston, TX33°F37°F95°F
Seattle, WA27°F43°F82°F

These are ENERGY STAR's county limits from the ASHRAE and Manual J design data; where a county has several weather stations, the guide uses the coldest. The 99% heating temperature is the one the outdoor air stays above 99% of the hours in a year, so the house is sized for nearly every night. Pick Other in the calculator to enter your own.

Heat Loss Through a Wall

One surface at a time, the formula is the area times the U-factor times the temperature difference. A 12 × 8 ft wall with no window, 96 square feet, at Chicago's 68°F difference:

Q = U × A × ΔTOlder wall, R-11 batts: 0.077 × 96 × 68 = 502 BTU/hWall built to 2021 code: 0.045 × 96 × 68 = 294 BTU/h

The U-factor is 1 divided by the wall's total R-value, including drywall, sheathing and the air films. Heat through 100 square feet at a 68°F difference, by R-value:

R-valueU-factorBTU/h per 100 sq ft
R-50.2001,360
R-110.091618
R-130.077523
R-190.053358
R-210.048324
R-300.033227
R-380.026179
R-490.020139

Each step up in R saves less than the one before: going from R-11 to R-21 cuts the loss by 294 BTU/h per 100 square feet, from R-30 to R-49 only 88. See how much insulation to add.

Heat Loss for One Room

For a single room, count only the surfaces that face outdoors or an unheated space. A 12 × 12 ft corner bedroom in the older house, under the attic, with two exterior walls and two 3 × 4 ft windows, in Chicago:

PartAreaBTU/h
Exterior walls168 sq ft878
Windows, double clear24 sq ft849
Ceiling under the attic144 sq ft500
Air leakage, 0.5 ACH1152 cu ft705
Total2,932

About 2,932 BTU an hour, 20.4 per square foot: more than the house average, because a corner room under the roof has more outside surface for its floor. A first-floor room with one outside wall and a heated room above loses far less. For cooling a room, size the cooling in BTU.

U-Factors Used

WindowU-factorR-value
Double, low-e0.28R-3.6
Double, clear0.52R-1.9
Single pane0.88R-1.1
  • Built to 2021 code: the code's maximum U-factors for climate zone 4: walls 0.045, ceiling 0.024, floor 0.047.
  • Older house: R-11 batts in the walls and floor and R-19 in the attic, with drywall, sheathing and air films: walls and floor about 0.077 to 0.080, ceiling 0.051.
  • Air leakage: 0.35 air changes an hour for a tight house, 0.5 average, 1 leaky.

For a house with a heat pump, the same loss sets its size at the design temperature; match a heat pump to it.

Frequently Asked Questions

How do you calculate heat loss?

For each surface, multiply its area by its U-factor and by the temperature difference: Q = U × A × ΔT. Add the air that leaks in: 1.08 × cfm × ΔT, where cfm is the house volume times the air changes per hour divided by 60. The sum is the heat loss in BTU per hour.

What is the heat loss of a 2,000 sq ft house?

About 38,295 BTU per hour for a two-story house with R-11 walls, an R-19 attic, double-pane windows and average air leakage in Chicago, where the design temperature is 2°F. Built to the 2021 energy code with low-e windows and tight construction, the same house loses about 22,669 BTU per hour.

What outdoor temperature should I use?

The 99% heating design temperature for your area: the temperature the outdoor air stays above 99% of the hours in a year. Manual J pairs it with 70°F indoors. ENERGY STAR publishes county limits, from 48°F in Miami-Dade to −14°F in Anchorage.

What is a U-factor?

The heat in BTU per hour that passes through one square foot for each degree Fahrenheit of difference. It is the inverse of the total R-value: an R-13 wall assembly has a U-factor of about 0.077.

Is heat loss the same as the furnace size?

It is what the furnace must replace on the coldest design day. A furnace's output should be 100% to 140% of the load, by ENERGY STAR's design rules; see the Furnace BTU Calculator.

How much heat is lost through windows?

In the default house, 10,608 BTU an hour, the largest single part, though windows are only 300 square feet. Clear double-pane glass has a U-factor of 0.52, against about 0.08 for an R-11 wall.

What is the heat loss per square foot of a house?

About 19.1 BTU an hour per square foot for the older house in Chicago, and 11.3 for the same house built to the 2021 energy code. Milder climates cut it in proportion to the temperature difference.

How do I calculate heat loss for a garage?

Enter the garage floor area as one story with its wall height. A 24 × 24 ft attached garage with 9 ft walls, R-11 walls, an R-19 ceiling and leaky doors at 1 air change an hour loses about 18,582 BTU an hour on Chicago's 2°F design day; an uninsulated one loses much more.

Which upgrade cuts heat loss the most?

In the default house, low-e windows in place of clear double-pane save about 4,896 BTU an hour, more than air sealing (2,938) or bringing the attic to code (1,839).

Sources

  • Carmody, J., & Haglund, K. (2012). Measure guideline: Energy-efficient window performance and selection (NREL/SR-5500-55444). U.S. Department of Energy, Building America.
  • ENERGY STAR. (2018). ENERGY STAR certified homes design temperature limit reference guide (rev. 09/01/2018). U.S. Environmental Protection Agency.
  • International Code Council. (2021). 2021 International energy conservation code (Table R402.1.2).
  • Nave, R. (n.d.-a). Calculating home heating energy. HyperPhysics, Georgia State University.
  • Nave, R. (n.d.-b). Insulation R-value [Table]. HyperPhysics, Georgia State University.
  • Sedine, J. D. (2018). An overview on ACCA's residential HVAC system design process [Presentation]. International Code Council.
  • Texas A&M University. (n.d.). COSC 325 lecture note #6: Heat loss and heat gain in buildings: Outside air.

Updated .

Cite this page as:

Daniel, P. Heat Loss Calculator. Available at: https://constructioncalculators.com/heat-loss-calculator/. Accessed: October 28, 2026.