Duct CFM Calculator

Enter your system's tons, a room's share of the house, or a known airflow to get the cfm and the round duct size that carries it.

16 in1,200 cfm3 tons
Airflow
tons

Duct

1,200cfm

3 tons × 400 cfm

Round metal ductcarries up to 1,352 cfm at 0.08 in. w.c. per 100 ft
16 in
Air velocityairflow ÷ duct area
859 fpm
Range350 humid to 450 dry, cfm a ton
1,050–1,350

How Much Airflow and What Size Duct?

A 3 ton system moves about 1,200 cfm at 400 cfm a ton. At a friction rate of 0.08 inches of water per 100 feet, that takes a 16 inch round metal duct, with the air moving at about 859 feet per minute. What each round duct carries at that friction rate:

5 in duct
60 cfm
6 in duct
98 cfm
7 in duct
148 cfm
8 in duct
212 cfm
9 in duct
291 cfm
10 in duct
386 cfm
12 in duct
628 cfm
14 in duct
948 cfm
16 in duct
1,352 cfm
CFM at 0.08 in. w.c. per 100 ft, in cfm

Doubling the diameter carries about six times the air, because the area grows four times and the friction falls.

How to Size a Duct by CFM

CFM = tons × cfm a ton; velocity = cfm ÷ duct area3 × 400 = 1,200 cfm16 in duct: π × (16 ÷ 24)² = 1.40 sq ft1,200 ÷ 1.40 = 859 fpm

The trunk carries the whole blower airflow; each branch carries one room's share. Manual D splits the airflow by each room's load; by floor area, a 300 square foot room in a 2,000 square foot house gets 15% of 1,200 cfm:

1,200 cfm180 cfm300 sq ft8 in120 cfm200 sq ft7 in90 cfm150 sq ft6 in36 cfm60 sq ft5 in
Living 300 sq ft: 180 cfm, 8 in · Bedroom 200 sq ft: 120 cfm, 7 in · Bedroom 150 sq ft: 90 cfm, 6 in · Bath 60 sq ft: 36 cfm, 5 in

Each branch is the smallest round duct that carries its airflow at 0.08. A room with big windows or a west wall takes more than its floor share; the Manual J room loads say how much.

Round Duct CFM Chart

Round ductCFM at 0.08CFM at 0.10
4 in3337
5 in6068
6 in98111
7 in148168
8 in212240
9 in291329
10 in386436
12 in628709
14 in9481,069
16 in1,3521,525
18 in1,8482,084
20 in2,4452,756

Straight, smooth galvanized duct with standard air, friction in inches of water per 100 feet, from the Darcy–Weisbach equation. Elbows, takeoffs and flex duct add friction; Manual D counts them in the total effective length.

Duct Size by System Tons

SystemAirflowRound trunkVelocity
1.5 tons600 cfm12 in764 fpm
2 tons800 cfm14 in748 fpm
2.5 tons1,000 cfm16 in716 fpm
3 tons1,200 cfm16 in859 fpm
3.5 tons1,400 cfm18 in792 fpm
4 tons1,600 cfm18 in905 fpm
5 tons2,000 cfm20 in917 fpm

At 400 cfm a ton and 0.08 inches of water per 100 feet. ACCA notes about 350 cfm a ton suits hot, humid climates and up to 450 dry ones; the Bonneville Power Administration recommends 375 to 425 with 350 the least. To size the system itself, find the AC tonnage.

Flex Duct and Return Air

The chart is for straight, smooth metal duct. Flexible duct has more friction for the same diameter, and much more when it sags, kinks or is left long and loose, so a flex run carries less than the chart shows. Keep flex runs short and pulled tight, support them along their length, and size them up when in doubt.

The return side carries the same air back to the blower, 1,200 cfm on a 3 ton system, so the return ducts and grilles together need at least the capacity of the supply. An undersized return keeps the blower from reaching its rated airflow.

Rectangular Duct to Round

A rectangular duct carries what a round duct of its equivalent diameter does, at the same friction. ASHRAE's equation, with the sides in inches:

Equivalent round = 1.30 × (a × b)^0.625 ÷ (a + b)^0.2512 × 8 in: 1.30 × 96^0.625 ÷ 20^0.25 = 10.7 in
RectangularEquivalent roundAirflow at 0.08
8 × 6 in7.6 in180 cfm
10 × 6 in8.4 in240 cfm
12 × 8 in10.7 in460 cfm
12 × 12 in13.1 in790 cfm
14 × 8 in11.5 in550 cfm
18 × 8 in12.9 in750 cfm
20 × 8 in13.5 in850 cfm
20 × 20 in21.9 in3,090 cfm
24 × 10 in16.5 in1,480 cfm

A 12 × 12 in duct carries about 790 cfm and a 20 × 20 in trunk about 3,090 at the same friction rate as the round chart. A flat duct carries less than a square one of the same area, because more of the air rubs on its walls: an 18 × 8 in duct has the same 144 square inches as a 12 × 12 but carries about 750 cfm.

Duct Design Steps

  • Blower airflow: from the cooling tons.
  • Room airflow: blower cfm × room load ÷ total load, the larger of heating and cooling.
  • Friction rate: available static pressure × 100 ÷ total effective length; the ICC's Manual D overview warns against always using 0.10.
  • Duct size: from the airflow and the friction rate, as in the chart.

For the whole system, furnace and fresh air included, use the HVAC calculator; for exhaust fans, work out the fan cfm.

Frequently Asked Questions

How many CFM per ton?

About 400 cfm per ton of cooling. ACCA notes 350 cfm a ton for hot, humid climates and 450 for drier ones; the Bonneville Power Administration recommends 375 to 425, with 350 the least.

What size duct for 1,200 CFM?

A 16 inch round metal duct at a friction rate of 0.08 inches of water per 100 feet, carrying up to about 1,352 cfm; at 0.10, a 16 inch duct too, since a 14 inch carries about 1,069.

How much CFM does a 6 inch duct carry?

About 98 cfm at 0.08 inches of water per 100 feet and 111 cfm at 0.10, in a straight, smooth metal run. Flex duct carries less, depending on how it is stretched.

How do I find the CFM for one room?

Manual D divides the blower airflow by each room's share of the load. By floor area, a 200 square foot room in a 2,000 square foot house gets 10% of 1,200 cfm: 120 cfm, a 7 inch duct.

What size duct for a 3 ton unit?

A 3 ton system moves about 1,200 cfm, which takes a 16 inch round trunk at 0.08 inches of water per 100 feet. Trunks are often rectangular instead; a 24 × 10 in duct, equal to a 16.5 in round, carries a little more.

How do I convert a rectangular duct to round?

Use the equivalent diameter: 1.30 × (a × b)^0.625 ÷ (a + b)^0.25, with the sides in inches. A 12 × 8 in duct equals a 10.7 in round duct for the same friction, so it carries a little more than a 10 in round.

How much CFM does a 4 inch duct carry?

About 33 cfm at 0.08 inches of water per 100 feet and 37 at 0.10, in a straight metal run. That suits a small bath fan, not a supply run.

What friction rate should I use?

Manual D calculates it from the blower's available static pressure and the longest duct run: FR = available static pressure × 100 ÷ total effective length. The ICC's Manual D overview warns against always using 0.10.

Sources

  • Akins, M. (2021, February 4). 400 CFM per ton, or is it? ACCA HVAC Blog.
  • ASHRAE. (2021). ASHRAE handbook: Fundamentals (Chapter 21, Duct design).
  • Bonneville Power Administration. (2011). Airflow test (detailed instructions) [PTCS].
  • Sedine, J. D. (2018). An overview on ACCA's residential HVAC system design process [Presentation]. International Code Council.

Updated .

Cite this page as:

Daniel, P. Duct CFM Calculator. Available at: https://constructioncalculators.com/duct-cfm-calculator/. Accessed: October 28, 2026.