How Many CFM Do I Need?
A 12 × 12 ft room with an 8 ft ceiling holds 1,152 cubic feet. Changing its air 5 times an hour, the CDC's aim for occupied rooms, takes 96 cfm. At the same 5 air changes and 8 ft ceilings, common rooms need:
The airflow grows with the room's volume, so a 10 ft ceiling needs a quarter more than an 8 ft one. That 96 cfm is fresh or filtered air for the people in the room; the heating and cooling supply to the same room is figured from its load, further down.
How to Calculate CFM for a Room
Multiply the length, width and height in feet for the volume, multiply by the air changes an hour you want, and divide by 60 minutes:
Turned around, ACH = cfm × 60 ÷ volume, the CDC's form for checking a room you already ventilate. Air changes for the 12 × 12 ft room:
| Air changes an hour | CFM |
|---|---|
| 0.35, HRV or ERV | 7 |
| 1 | 19 |
| 3 | 58 |
| 5, CDC aim | 96 |
| 8, bathroom | 154 |
| 10 | 192 |
Only a few air change rates have a published basis: 5 or more for occupied rooms (CDC), about 8 for bathrooms (HVI's 1 cfm per square foot), 5 for continuous kitchen exhaust (ENERGY STAR) and 0.35 for a whole house through a heat or energy recovery ventilator (HVI). The CDC adds that 5 air changes do not guarantee safe air, and that air cleaned by a filter counts toward the total.
Whole-House Ventilation
The IRC sets continuous fresh air by floor area and bedrooms; a 2,000 square foot house with 3 bedrooms needs 60 cfm. Its equation, 0.01 × floor area + 7.5 × (bedrooms + 1), gives 50, and ASHRAE 62.2, at 0.03 × floor area, gives 90.
| Floor area, sq ft | 0–1 BR | 2–3 BR | 4–5 BR | 6–7 BR | Over 7 BR |
|---|---|---|---|---|---|
| Up to 1,500 | 30 | 45 | 60 | 75 | 90 |
| 1,501–3,000 | 45 | 60 | 75 | 90 | 105 |
| 3,001–4,500 | 60 | 75 | 90 | 105 | 120 |
| 4,501–6,000 | 75 | 90 | 105 | 120 | 135 |
| 6,001–7,500 | 90 | 105 | 120 | 135 | 150 |
| Over 7,500 | 105 | 120 | 135 | 150 | 165 |
A fan that runs only part of the time has to move more while it runs: by the IRC's second table, twice the rate at 50% run time and four times at 25%. HVI sizes a heat or energy recovery ventilator at about 5 cfm per 100 square feet, 100 cfm for 2,000 square feet.
CFM per Room for Heating and Cooling
Supply air from a furnace or air conditioner is a different number from fresh air: it is mostly house air going round again. ACCA's Manual D splits the blower's airflow among the rooms by each room's share of the heating or cooling load:
Floor area stands in for the load in that example. Rooms in the same 2,000 square foot house:
| Room | Sq ft | Supply air |
|---|---|---|
| 10 × 10 ft | 100 | 60 cfm |
| 12 × 12 ft | 144 | 86 cfm |
| 12 × 15 ft | 180 | 108 cfm |
| 15 × 20 ft | 300 | 180 cfm |
| 20 × 20 ft | 400 | 240 cfm |
That works out to 0.6 cfm per square foot. The DOE quotes the common rule of one ton of cooling per 400 to 500 square feet, which at 400 cfm a ton is 0.8 to 1.0 cfm per square foot. A room with big west windows or one over a garage carries more than its floor share, which is why a room-by-room load calculation decides the final airflow. Pick the duct size for each run.
The blower's airflow per ton of cooling, by climate, as ACCA describes it:
| System | Humid | Typical | Dry |
|---|---|---|---|
| 1.5 tons | 525 | 600 | 675 |
| 2 tons | 700 | 800 | 900 |
| 2.5 tons | 875 | 1,000 | 1,125 |
| 3 tons | 1,050 | 1,200 | 1,350 |
| 3.5 tons | 1,225 | 1,400 | 1,575 |
| 4 tons | 1,400 | 1,600 | 1,800 |
| 5 tons | 1,750 | 2,000 | 2,250 |
| System | BTU per hour | Humid, 350 | Typical, 400 | Dry, 450 |
|---|---|---|---|---|
| 1.5 tons | 18,000 | 525 | 600 | 675 |
| 2 tons | 24,000 | 700 | 800 | 900 |
| 2.5 tons | 30,000 | 875 | 1,000 | 1,125 |
| 3 tons | 36,000 | 1,050 | 1,200 | 1,350 |
| 3.5 tons | 42,000 | 1,225 | 1,400 | 1,575 |
| 4 tons | 48,000 | 1,400 | 1,600 | 1,800 |
| 5 tons | 60,000 | 1,750 | 2,000 | 2,250 |
Range Hood CFM
HVI recommends 100 cfm per foot of range for a hood against a wall and 150 per foot for one over an island; the least it accepts is 40 and 50. For a 30 inch range:
A recirculating hood filters the air and blows it back into the kitchen, so HVI counts it as no ventilation. The IRC asks for 100 cfm of intermittent kitchen exhaust, or 25 cfm continuous.
Big hoods bring a code question. Where a gas, oil or wood-burning appliance that is neither direct-vent nor mechanically vented sits inside the house's air barrier, such as an atmospheric water heater, the IRC requires makeup air for any hood able to exhaust more than 400 cfm: outdoor air at about the exhaust rate, through a duct with a damper. A 36 inch range over an island at HVI's 150 cfm a foot needs 450 cfm and crosses that line; against a wall it needs 300.
CFM50 and ACH50 From a Blower Door Test
A blower door test reports how leaky a house is as CFM50, the airflow the fan pulls through the gaps at 50 pascals of pressure. Divide by the house's volume the same way as for a room: ACH50 = CFM50 × 60 ÷ volume. The 2021 IECC caps new houses at 5 ACH50 in the warmest climate zones, 1 and 2, and at 3 ACH50 in zones 3 through 8. The largest CFM50 that passes, with 8 ft ceilings:
A 2,000 square foot house holds 16,000 cubic feet, so it passes at 3 ACH50 with up to 800 CFM50. Tightness and fresh air go together: the IRC requires the whole-house ventilation above once a house tests at 5 ACH50 or less.
How to Measure CFM in a Duct
Airflow in a duct is the air speed times the duct's cross-section. Measure the speed in feet per minute with an anemometer at several points across the opening and average them:
Run the other way, the same formula gives the speed: cfm ÷ area = fpm. How much a round duct can carry depends on the friction allowed per 100 feet of run. At 0.08 and 0.10 inch of water per 100 feet, the two rates the duct calculator offers, straight smooth metal duct carries:
| Round duct | 0.08 in. w.c. | 0.10 in. w.c. |
|---|---|---|
| 4 in | 33 cfm | 37 cfm |
| 5 in | 60 cfm | 68 cfm |
| 6 in | 98 cfm | 111 cfm |
| 7 in | 148 cfm | 168 cfm |
| 8 in | 212 cfm | 240 cfm |
| 9 in | 291 cfm | 329 cfm |
| 10 in | 386 cfm | 436 cfm |
| 12 in | 628 cfm | 709 cfm |
| 14 in | 948 cfm | 1069 cfm |
An 8 inch duct carries 212 to 240 cfm, so the 244 cfm measured above at 700 fpm is a little more than it carries even at 0.10 inch. Fittings and flex duct add friction and lower these numbers; our duct CFM calculator picks a size for a given airflow.
CFM to m³/h, L/s and BTU
One cubic foot is 0.0283 cubic meters, so 1 cfm is 1.70 m³/h, 0.47 L/s or 28.3 L/min:
| Airflow | m³/h | L/s | L/min |
|---|---|---|---|
| 100 cfm | 170 m³/h | 47 L/s | 2,832 L/min |
| 500 cfm | 850 m³/h | 236 L/s | 14,158 L/min |
| 1,000 cfm | 1,699 m³/h | 472 L/s | 28,317 L/min |
| 2,000 cfm | 3,398 m³/h | 944 L/s | 56,634 L/min |
CFM is a flow of air, not of heat; the heat it carries depends on how much the air is warmed or cooled. In the sensible heat formula, Q = 1.08 × cfm × ΔT in BTU per hour: 1,200 cfm cooled by 20°F carries 25,920 BTU per hour. Work out the BTU a room needs for heating or cooling it.
Bathrooms, Whole-House Fans and Cooling
- Bathroom: 50 cfm intermittent or 20 cfm continuous by the IRC; HVI recommends 1 cfm per square foot up to 100 square feet. Size the bathroom fan for your room.
- Whole-house attic fan: HVI multiplies the floor area by 3 for about one air change every two minutes: 6,000 cfm for 2,000 square feet.
- Heating and cooling: the blower moves about 400 cfm per ton of cooling, 1,200 cfm for 3 tons; Building Science Corporation gives 350 to 400 in humid climates and 400 to 425 in dry ones. Size the HVAC system for the whole house.
Frequently Asked Questions
How do I calculate CFM for a room?
Multiply the room's length, width and height in feet for its volume, multiply by the air changes per hour you want and divide by 60. A 12 × 12 ft room with an 8 ft ceiling at 5 air changes an hour needs 1,152 × 5 ÷ 60 = 96 cfm.
How many air changes per hour does a room need?
The CDC says to aim for 5 or more air changes an hour in occupied rooms to reduce airborne viruses, counting filtration. HVI's 1 cfm per square foot for bathrooms is about 8 an hour, and ENERGY STAR sets 5 for continuous kitchen exhaust.
How much fresh air does a house need?
The IRC requires 60 cfm of continuous whole-house ventilation for 1,501 to 3,000 square feet with 2 or 3 bedrooms. ASHRAE 62.2 asks for 0.03 cfm per square foot plus 7.5 cfm for each bedroom plus one: 90 cfm for 2,000 square feet and 3 bedrooms.
How many CFM do I need for a 3,000 sq ft house?
For fresh air, 60 cfm continuous with 2 or 3 bedrooms and 75 with 4 or 5, by the IRC table; ASHRAE 62.2 asks for 120 cfm with 3 bedrooms. The heating and cooling blower moves far more, about 400 cfm for each ton of the system.
What CFM range hood do I need?
HVI recommends 100 cfm per foot of range against a wall, 40 at the least, and 150 per foot over an island, 50 at the least: 250 cfm for a 30 inch range on a wall. Above 400 cfm the IRC can require makeup air.
How do I convert CFM to air changes per hour?
ACH = cfm × 60 ÷ room volume in cubic feet. 96 cfm in a 1,152 cubic foot room is 5 air changes an hour. A blower door's CFM50 converts the same way to ACH50.
How many CFM per square foot?
It depends on what the air is for. HVI gives 1 cfm per square foot for a bathroom up to 100 square feet and about 3 for a whole-house attic fan; ASHRAE 62.2 asks for 0.03 per square foot of continuous fresh air, plus 7.5 for each bedroom plus one. Heating and cooling supply air is about 0.6 cfm per square foot in a 2,000 square foot house on a 3 ton system.
What CFM bathroom fan do I need?
HVI recommends 1 cfm per square foot for bathrooms up to 100 square feet, at least 50 cfm; the IRC requires 50 cfm intermittent or 20 cfm continuous. Larger bathrooms are sized by their fixtures.
What size whole-house fan do I need?
HVI multiplies the floor area by 3 for about one air change every two minutes at 8 ft ceilings: about 6,000 cfm for a 2,000 square foot house.
How many CFM per ton of air conditioning?
About 400 cfm per ton, so a 3 ton system moves about 1,200 cfm. ACCA puts about 350 in hot, humid climates and up to 450 in dry ones; Building Science Corporation gives 350 to 400 in humid climates and 400 to 425 in dry ones.
Sources
- Akins, M. (2021, February 4). 400 CFM per ton, or is it? ACCA HVAC Blog.
- ASHRAE. (2015). Addendum m to ANSI/ASHRAE Standard 62.2-2013: Ventilation and acceptable indoor air quality in low-rise residential buildings.
- ASHRAE. (2021). ASHRAE handbook: Fundamentals (Chapter 21, Duct design).
- Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health. (2024, October 3). How much ventilation is enough?
- ENERGY STAR. (2025). National HVAC design supplement to Std. 310 for dwellings & units (Rev. 14).
- Home Ventilating Institute. (n.d.). How much ventilation do I need?
- International Code Council. (2020a). 2021 International Energy Conservation Code (Section R402.4.1.2).
- International Code Council. (2020b). 2021 International Residential Code (Sections R303.4, M1503.6, M1505.4 and Table M1505.4.3(1)).
- National Institute of Standards and Technology. (n.d.). NIST guide to the SI, Appendix B.9: Factors for units listed by kind of quantity.
- Oregon Building Codes Division. (2021). Balanced mechanical whole-house ventilation strategies [Technical bulletin].
- Rudd, A. (2006). Design process for sizing: Cooling and heating system capacity, room air flows, trunk and runout ducts, and transfer air ducts (GM-0605). Building Science Corporation.
- Sedine, J. D. (2018). An overview on ACCA's residential HVAC system design process [Presentation]. International Code Council.
- Texas A&M University. (n.d.). COSC 325 lecture note #6: Heat loss and heat gain in buildings: Outside air.
- U.S. Department of Energy. (2021). Consumer guide to home heating and cooling (DOE/EE-2464).
Updated .
Cite this page as:
Daniel, P. CFM Calculator. Available at: https://constructioncalculators.com/cfm-calculator/. Accessed: October 28, 2026.